Overload protection |
105%~125%
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
Over voltage protection |
5.75~6.75V, 13.8~16.8V, 17~20.5V, 27.6~32.4V, 31~36.5V, 56.6~66.2V
Protection type : Shut down o/p voltage, re-power on to recover |
Over Temperature |
Shut down o/p voltage, recovers automatically after temperature goes down |
Working temperature |
-30°C ~ 70°C (refer to "Derating Curve") |
Safety standards |
UL62368-1, CSA C22.2 No. 62368-1, TUV EN62368-1, CCC GB4943.1, BSMI CNS14336-1, AS/NZS62368.1, EAC TP TC 004 approved |
Withstand voltage |
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC |
EMC IMMUNITY |
EN55024, EN61000-6-2, CCC GB17625.1,GB/T9254, BSMI CNS13438 |
ESD |
EN61000-4-2 |
Level 3, 8KV air ; Level 2, 4KV contact |
Surge |
EN61000-4-5 |
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line |
Voltage Dips and Interruptions |
EN61000-4-11 |
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods |
MTBF |
336.9K hrs min. Telcordia SR-332 (Bellcore) ; 109.1K hrs min. MIL-HDBK-217F (25℃) |
Packing |
1.64kg; 6pcs / 10.8Kg / 1.1CUFT |