Input Voltage
Range
|
90 ~ 132VAC / 180 ~ 264VAC by switch
240 ~ 370VDC (switch on 230VAC) |
AC Inrush Current (Typ.) |
COLD STAR 60A/115VAC 60A/230VAC |
Overload protection |
110 ~ 140% rated output power
3.3~36V Hiccup mode, recovers automatically after fault condition is removed.
48V Shut down and latch off o/p voltage, re-power on to recover. |
Over voltage protection |
3.8~4.45V, 4.6~5.4V, 5.75~6.75V, 13.8~16.2V,
18~21V, 28.8~33.6V, 41.4~46.8V, 55.2~64.8V
3.3~36V Hiccup mode, recovers automatically after fault condition is removed.
48V Shut down and latch off o/p voltage, re-power on to recover. |
Working temperature |
-25°C ~ +70°C (refer to "Derating Curve") |
Vibration |
10~500Hz, 5G 10min/1 cycle, period for 60 min
each along X, Y, Z axes |
Safety standards |
IEC/UL 62368-1, BSMI CNS14336-1,EAC TP TC 004, KC K60950-1(for LRS-200-12/24 only),
BIS IS13252(Part1): 2010/IEC 60950-1: 2005, AS/NZS62368.1 approved; Design refer to BS EN/EN62368-1 |
Withstand voltage |
I/P-O/P: 3KVAC,
I/P-FG: 2KVAC,
O/P-FG: 0.5KVAC |
EMC EMISSION |
Compliance to BSMI CNS13438, EAC TP TC 020,KC KN32,KN35(for LRS-200-12/24 only) |
EMC IMMUNITY |
Compliance to BS EN/EN55035, EAC TP TC 020,KC KN32,KN35(for LRS-200-12/24 only) |
MTBF |
2346.6K hrs min. Telcordia SR-332 (Bellcore) ; 279.4Khrs min. MIL-HDBK-217F (25℃) |
Packing |
0.66Kg, 15PCS/ 10.9Kg/ 0.78CUFT |