AC Inrush Current (Typ.) |
0.5 A (rms) for 115 VAC
0.3 A (rms) for 230 VAC |
Over Voltage protection |
Set at 116% to 230% of its nominal
output voltage |
Withstand voltage |
4000 VAC from input to output |
EMC Conduction & Radiation |
EN55011: Class B conducted, Class B radiated
FCC: Class B conducted, Class B radiated
VCCI: Class B conducted, Class B radiated
EN61000-3-2: Harmonic distortion, Class A and D
EN61000-3-3: Line flicker
EN61000-4-2: ESD, ±8 KV air and +/-6 KV contact
EN61000-4-3: Radiated immunity, 3 V/m
EN61000-4-4: Fast transient/burst, +/-2 KV
EN61000-4-5: Surge, ±1 KV diff., +/-2 KV com.
EN61000-4-6: Conducted immunity, 3 Vrms
EN61000-4-8: Magnetic field immunity, 3 A/m
EN61000-4-11: Voltage dip immunity, 30% reduction for
500
ms, 60% reduction for 100 ms, and >95% reduction for
10 ms
(LVD)
RoHS
PMP15 SERIES |
Packing |
1.5kg; 8pcs / 13.0kg / 1.1CUFT |