AC input voltage
range |
90 ~ 305VAC 127 ~ 431VDC
(Please refer to "STATIC CHARACTERISTIC" section) |
Power Factor (Typ.)
|
PF≧0.98/115VAC, PF≧0.95/230VAC, PF≧0.92/277VAC @ full load
(Please refer to "POWER FACTOR (PF) CHARACTERISTIC" section) |
Over Voltage protection |
125%~140%
Constant current limiting, recovers automatically after fault condition is removed |
OVER TEMPERATURE |
18 ~ 24V, 23 ~ 30V, 28 ~ 35V, 35 ~ 43V, 41 ~ 49V, 48 ~ 58V, 54 ~ 65V, 59 ~ 68V
Shut down o/p voltage, re-power on to recover |
Withstand voltage |
I/P-O/P:3.75KVAC
I/P-FG:2KVAC
O/P-FG:1.5KVAC |
Working temperature |
Tcase= -40 ~ +80℃(Please refer to "OUTPUT LOAD vs TEMPERATURE" section) |
Safety standards |
UL8750(type"HL"), CSA C22.2 No. 250.0-08 (except for 48V, 54V), TUV EN61347-1, EN61347-2-13 independent, IP65 or IP67 approved ;optional models for J61347-1, J61347-2-13 ; design refer to UL60950-1, TUV EN60950-1, EN60335-1 |
EMC EMISSION |
Compliance to EN55015, EN61000-3-2 Class C (@ load≧60%) ; EN61000-3-3 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11; EN61547, light industry level (surge immunity Line-Earth 4KV, Line-Line 2KV) |
MTBF |
1132K hrs min. Telcordia SR-332 (Bellcore) ; 338K hrs min. MIL-HDBK-217F (25℃) |
Packing |
0.73Kg; 20pcs/15.6Kg/0.9CUFT |