AC input voltage
range |
180 ~ 550VAC , 254 ~ 780VDC |
Over Load Protection |
105 ~ 130% rated output, power
Protection type :
Constant current limiting, recovers automatically
after fault condition is removed |
Over voltage Protection |
29 ~ 33V, 56 ~ 65V
Protection type : Shut down o/p voltage, auto-recovery after 1 minute if the fault condition is removed |
Withstand Voltage |
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC |
Working Temperature |
-30 ~ +70°C (Refer to output load derating
curve) |
Safety standards |
UL508, AS/NZS 62368.1, EAC TP TC 004 approved, IEC62368-1 CB approved by SIQ, design refer to GL;(meet EN60204-1) |
EMC EMISSION |
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020 approved |
MTBF |
112.8K hrs min. MIL-HDBK-217F (25℃) |
Packing |
1.7Kg; 8pcs/14.6Kg/0.9CUFT |
Dimension |
85.5*125.2*128.5mm (W*H*D) |