AC input voltage
range |
180 ~ 550VAC , 254 ~ 780VDC |
Over Load Protection |
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
Over voltage Protection |
16 ~ 18V, 31 ~ 37V, 60 ~ 67V
Protection type : Shut down o/p voltage,
re-power on to recover |
Withstand Voltage |
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC |
Working Temperature |
-25 ~ +70°C (Refer to output load derating
curve) |
Safety standards |
UL508, AS/NZS 62368.1, EAC TP TC 004 approved, IEC62368-1 CB approved by SIQ;(meet EN60204-1) |
EMC EMISSION |
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EAC TP TC 020 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020 |
MTBF |
268K hrs min. MIL-HDBK-217F (25℃) |
Packing |
0.65Kg; 20pcs/14Kg/1.16CUFT |