AC input voltage
range |
Three-Phase 340 ~ 550VAC (Dual phase operation possible in connecting L1, L3, FG or L2, L3,FG)or 480 ~ 780VDC |
Over Load Protection |
105% ~ 130% rated output
power
Protection type : Constant current limiting, unit will shut down after 3 sec. |
Over voltage Protection |
30~36V, 56~65V
Protection type : Hiccup mode, recovers automatically after fault condition is removed. |
Over Temperature |
Shut down o/p voltage, recovers automatically after temperature goes down |
Withstand Voltage |
I/P-O/P: 4.87KVAC
I/P-FG: 2.4KVAC
O/P-FG: 0.5KVAC
O/P-DC OK: 0.5KVAC |
Working Temperature |
-30°C ~ 70°C (refer to output derating curve) |
Safety standards |
UL61010-1, UL61010-2-201, EN61558-1, EN61558-2-16, EAC TP TC 004 approved |
Conducted |
EN55032(CISPR32)/EN61204-3 |
Class B |
Radiated |
EN55032(CISPR32)/EN61204-3 |
Class B |
ESD |
EN61000-4-2 |
Level 4, 15KV air ; Level 4, 8KV contact |
Surge |
EN61000-4-5 |
Level 4, 2KV / Line-Line, Level 4, 4KV/ Line-Earth |
Voltage Dips and Interruptions |
EN61000-4-11 |
>95% dip 0.5 periods, 30% dip 25 periods > 95% interruptions 250 periods |
MTBF |
515.4K hrs min. Telcordia SR-332(Bellcore) ; 215.6K hrs min. MIL-HDBK-217F (25℃) |
Packing |
1Kg ; 12pcs/13Kg/1.06CUFT |