AC input voltage
range |
180 ~ 264VAC 254 ~ 370VDC |
Over Load Protection |
Normally works within 105% ~ 130% rated output
power for more than 3 sec and then shut down o/p voltage with
auto-recovery, after 30 seconds if the peak load condition is removed
Constant current limiting within 130 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage, re-power
on to recover |
Over voltage Protection |
29~33V, 56~65V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery |
Over Temperature |
Shut down o/p voltage, recovers automatically after temperature goes down |
Withstand Voltage |
I/P-O/P: 3KVAC
I/P-FG: 2KVAC
O/P-FG: 0.5KVAC
O/P-DC OK: 0.5KVAC |
Working Temperature |
-30°C ~ 70°C (refer to output derating curve) |
Safety standards |
UL508, TUV EN62368-1, BSMI CNS14336-1, AS/NZS62368.1, EAC TP TC 004 approved ; (meet EN60204-1) |
EMC EMISSION |
Compliance to EN55032 (CISPR32), EN61204-3 Conduction class B, Radiation class A, EN61000-3-2,-3, EAC TP TC 020, BSMI CNS13438 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020 |
MTBF |
69.8K hrs min. MIL-HDBK-217F (25℃) |
Packing |
2.47Kg ; 6pcs/15.8Kg/1.55CUFT |