AC input voltage
range |
88 ~ 264VAC 124 ~ 370VDC [DC input operation possible by connecting AC/L(+),AC/N(-)] |
Over Load Protection |
Normally works within 110% ~ 150% rated output
power for more than 3 sec and then shut down o/p
voltage, re-powr on to recover
150 ~170% rated power, constant current limiting
with auto-recovery within 3 seconds, and then shut
down o/p voltage after 3 seconds, re-power ont to
recover |
Over voltage Protection |
14~17V, 29~33V, 56~65V
Protection type: Shut down o/p voltage, re-power
on to recover |
Withstand Voltage |
I/P-O/P: 3KVAC
I/P-FG: 2KVAC
O/P-FG: 0.5KVAC |
Working Temperature |
-30°C ~ +70°C (refer to derating curve) |
Safety standards |
UL508, TUV EN62368-1, AS/NZS 62368.1, EAC TP TC 004 approved, design refer to GL |
EMC EMISSION |
Compliance to EN55032 (CISPR32). EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020, SEMI F47 approved |
MTBF |
481.9K hrs min. MIL-HDBK-217F (25℃) |
Packing |
0.51Kg; 28pcs/15.3Kg/1.22CUFT |