Over Load Protection |
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds |
Over voltage Protection |
29~33V, 56~65V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery |
Withstand Voltage |
I/P-O/P: 3KVAC
I/P-FG: 2KVAC
O/P-FG: 0.5KVAC
O/P-DC OK: 0.5KVAC |
Working Temperature |
-25°C ~ 70°C (refer to output derating curve) |
Safety standards |
UL508, TUV EN62368-1, EAC TP TC 004 , BSMI CNS14336-1 approved ; (meet EN60204-1) |
EMC EMISSION |
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020, CNS13438 |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020, SEMI F47 approved |
MTBF |
112.9K hrs min. MIL-HDBK-217F (25℃) |
Packing |
1.6Kg; 8pcs/13.8Kg/0.9CUFT |
Dimension |
85.5*125.2*128.5mm (W*H*D) |