Over Load Protection |
Normally works within 110% ~ 150% rated output
power for more than 3 sec and then shut down o/p
voltage >150 rated power, constant current
limiting with auto-recovery within 3 seconds and
shut down o/p voltage after 3 seconds |
Over voltage Protection |
14~17V, 29~33V, 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover |
Withstand Voltage |
I/P-O/P: 3KVAC
I/P-FG: 2KVAC
O/P-FG: 0.5KVAC
O/P-DC OK: 0.5KVAC |
Working Temperature |
-25°C ~ 70°C (refer to output derating curve) |
Safety standards |
UL508, TUV EN62368-1, EAC TP TC 004 approved , BSMI CNS14336-1 ;(meet EN60204-1) |
EMC EMISSION |
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B |
EMC IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020, SEMI F47 approved |
MTBF |
289.9K hrs min. MIL-HDBK-217F (25℃) |
Packing |
0.67Kg; 20pcs/14.4Kg/1.16CUFT |