DC OUTPUT VOLTAGE WITHOUT CHOKE |
30V(Additional output for ancillary power) |
VOLTAGE RANGE |
180 ~ 264VAC 230 ~ 370VDC |
OVERLOAD |
205 ~ 235% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
OVER VOLTAGE |
33 ~ 35V
Protection type : Shut down o/p voltage, re-power on to recover |
WORKING TEMP. |
-30 ~ +70℃ (Refer to "Derating Curve") |
SAFETY STANDARDS |
EN61558-1,EN61558-2-16;EN50491-3, EAC TP TC 004 approved |
EMC EMISSION |
Compliance to EN50491-5-2,-5-3;EN61000-3-2,-3-3, EAC TP TC 020 |
EMC IMMUNITY |
Compliance to EN50491-5-2,-5-3;EN61000-4-2,3,4,5,6,8,11, heavy industry level, criteria A, EAC TP TC 020 |
MTBF |
109K hrs min. MIL-HDBK-217F (25℃) |
MOUNTING |
35mm mounting rail according to DIN EN60715 |
PACKING |
0.215Kg ; 60pcs/13.9Kg/0.97CUFT |