Power Supply DBU-3200
Features : * Charger for lead-acid batteries (flooded, Gel and AGM) and Li-ion batteries (lithium iron and lithium manganese)
* Built-in default 3 stage charging curves and programmable curve
* Built-in l2C interface, PMBus protocol (Optional CANBus protocol)
* Universal AC input / Full range
* Built-in active PFC function
* Forced air cooling by built-in thermal controlled DC fan
* Output voltage and current programmable
* Built-in OR-ing FET
* Active vurrent sharing up to 6400W(2+1)
* Protection: Battery under voltage/ Battery no connection/ Short circuit/ Over voltage/ Over temperature
* Optional conformal coating
* 5 years warranty
Model No. : DBU-3200
AC input voltage range 90~264VAC, 127~370VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR (Typ.) 0.97/230VAC at full load
Inrush Current (Typ.) COLD START 55A/230VAC
LEAKAGE CURRENT <2mA / 230VAC
OVER VOLTAGE 31.5 ~ 37.5V, 63 ~ 75V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE Shut down o/p voltage, recovers automatically after temperature goes down
Withstand voltage I/P-O/P: 3K VAC,
I/P-FG: 2K VAC,
O/P-FG: 1.5KVAC
Working temperature -30°C ~ +70°C ( refer to output derating curve )
Safety standards UL62368-1, CSA C22.2 No. 62368-1, TUV EN62368-1, EAC TP TC 004 approved
EMC EMISSION Parameter Standard Test Level / Note
Conducted EN55032 (CISPR32) Class B
Radiated EN55032 (CISPR32) Class A
Harmonic Current EN61000-3-2 ---
Voltage Flicker EN61000-3-3 ---
EMC IMMUNITY EN55024, EN61000-6-2
Parameter Standard Test Level / Note
ESD EN61000-4-2 Level 3, 8KV air ; Level 2, 4KV contact
Radiated EN61000-4-3 Level 3
EFT / Burst EN61000-4-4 Level 3
Surge EN61000-4-5 2KV/Line-Line 4KV/Line-Earth
Conducted EN61000-4-6 Level 3
Magnetic Field EN61000-4-8 Level 4
Voltage Dips and Interruptions EN61000-4-11 >95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
MTBF 160.1K hrs min. Telcordia SR-332 (Bellcore) ; 38.9K hrs min. MIL-HDBK-217F (25℃)
DIMENSION 325.8*107*41mm (L*W*H)
PACKING 2.76Kg;4pcs/12Kg/0.83CUFT
P/No. BOOST CHARGE VOLTAGE Vboost
FLOAT CHARGE VOLTAGE(Vfloat)(default)
CONSTANT CURRENT(CC)(default)
Effi.
DBU-3200-24 28.8V 27.6V 110A 93.5%
DBU-3200--48 57.6V 55.2V 55A 94.5%
 